Cooling Towers Cooling TowersHOMESite MapCooling TowersAbout UsFinancingEngineering DataPhoto GalleryCooling Tower SystemsWarrantyContact UsAssembly Instructions
Engineering Information

Cooling Tower Specifications / Drawings

Engineering Brochure

Cooling Tower Assembly Man Hours

Assembly Drawings & Parts

Motor Drawings

V Belt Speed Reducer Replacement
Parts Drawings


Heater and Control Panel Specifications

Heat Exchangers

Water Pump Selection


Product Literature
& List Price

T-2 Cooling Tower Sets List Price

T-2 Model Cooling Tower
Replacement List Price

Low Noise Cooling Tower List Price

Stainless Steel Optional
Add-On List Price

Fan Motor List Price

V Belt List Price

V Belt Speed Reducer
Replacement Parts List Price

Extension Skirt List Price

Winterization Basin Heaters &
Heater Control Panel

Vibration Isolation Mounts List Price

Request For Quote
Cooling Tower Selection

Water Pump Selection
New Surplus Parts & Equipment
Photo Gallery
Terms & Conditions
Warranty

 

Trouble Analysis Table

Download the Complete Operating Instructions & Service Manual in PDF format  

(274 KB, requires Adobe Acrobat Reader)

 

Trouble Causes Counter-Measures
Rise in cooling water temperature
  1. Excess or inadequate cooling water flow.

  2. Irregular flow of air.

  3. Recirculation of air exhausted from tower.

  4. Irregular operation of sprinkler pipes.

  5. Improper flow of air.

  6. Blocking of the filling.

  1. Adjust to the specified flow.

  2. Improve ventilation.

  3. Same as above or install baffles.

  4. Remove dust and scale.

  5. Adjust the angle of fan blades.

  6. Clean the blocked areas.

Drop in the volume of cooling water
  1. Blocking of the sprinkler pipe holes.

  2. Blocking of strainer mesh.

  3. Drop in the water level of water basin.

  4. Improper selection of water circulating pump.

  1. See section for maintenance and adjustment.

  2. Remove strainer and clean.

  3. Adjust float valve.

  4. Replace the pump with one matching planned volume of water.

Noise and vibration
  1. Fan blade tips touching fan stack.
  2. Improper mounting of fan blades.
  3. Loose belts.
  4. Shortage of speed reducer oil.
  1. Adjust the fan mounting.
  2. Correct the blade angle settings.
  3. Tighten loose bolts.
  4. Supply oil up to the level specified.
Excessive current draw
  1. Drop in voltage.
  2. Irregularities in the angles of the fan blades.
  3. Overload through excess airflow.
  1. Check supply voltage.  Notify power company if necessary.
  2. Adjust fan blade angles.
  3. Adjust fan blade angles.
Water carry over
  1. Irregular operation of sprinkler pipes.
  2. Blocking of the filling.
  3. Defective eliminator.
  4. Too much circulating water.
  1. Adjust the angle of the sprinkler pipes in the sprinkler head.
  2. Eliminate blockage at the upper edge of the filling.
  3. Renew the eliminator.
  4. Adjust the water flow by means of the valve.